Reduced running costs
The technology cabinet with a dedicated air-conditioned space for the KSBM4/TN-P-H batteries is designed for placing 19″ technology in an outdoor environment with the possibility of maintaining a constant temperature for the batteries and forced ventilation of the heat loss of the installed technology depending on the surrounding weather conditions. The stable temperature of the battery compartment is ensured by semiconductor technology using the Peltier principle, which ensures lower operating costs for energy and a reduction in cabinet noise.
KSBM4/TN-P-H is equipped with a 48V DC power supply with power according to the number of installed rectifier modules, with battery protection against deep discharge (LVD and 2 x PLD) and three 48V battery sets in front terminal design.
They are intended for backing up telecommunications, security or control technologies in an outdoor environment with regard to ecology, saving electricity and preserving the longest possible life of batteries.
- A pair of lockable doors with 3-point locking
- The integrated AC distribution fully replaces the TGBT switchgear (reduction of space requirements as well as costs).
- Possibility of remote reading of the status of the billing electricity meter (provided the addition of an optical converter and the use of a compatible electricity meter).
- Possibility of remote monitoring via camera.
- The possibility of remote monitoring of the status of the entire site, as well as the possibility of remote management and parameter setting.
- AC distribution – input switch, overvoltage protection, control of the presence of the AC power network, motor drive of the input AC source circuit breaker, service socket with current protector, terminals for connecting a mobile motor generator.
- Aviation warning lighting power supply DC distribution – six separate sections with fuse monitoring, consumption measurement and definable cut-off level.
- CELLD300E 9SH source with two DPS850-6RS grids for DPR850B-48 rectifiers.
- ORION control unit. 19″ racks for placing technology.
- Dedicated air-conditioned space for batteries. Thermoelectric air conditioning unit PK300 with heat exchanger.
- The technological space is ventilated using a fan located under the roof of the cabinet, the speed of which is regulated by the temperature of the ventilated space and heated by a heating element with an input of 250 W.
- LED lighting 48 V DC located on the ceiling of the cabinet and portable LED light 230 V AC with movable supply, door contacts, 2 x LSA strip with output alarms.
- Sagemcom ESM communicator and power meter for remote monitoring via GSM network.
- 6 output and 3 battery metering shunts, 5 sections of output DC circuit breakers on the technology side.
- Filters against the ingress of dust into the cabinet space with easy handling during replacement.
- Preparation for connecting photovoltaic panels with max. with an input power of 1000 Wp.
- The possibility of implementing a hybrid network power supply using solar and wind energy.
- Roof with eyelets for handling with the help of a lifting device.
- Base with holes for fixing the cabinet to the supporting structure.