{"id":8551,"date":"2024-03-14T09:41:16","date_gmt":"2024-03-14T08:41:16","guid":{"rendered":"https:\/\/a2b.sk\/uncategorized\/dps-series\/"},"modified":"2024-07-11T10:00:47","modified_gmt":"2024-07-11T08:00:47","slug":"dps-series","status":"publish","type":"post","link":"https:\/\/a2b.sk\/en\/ups-systems\/on-line-vfi-above-to-10-kva\/dps-series\/","title":{"rendered":"DPS Series"},"content":{"rendered":"\n<p>Delta\u2019s Ultron DPS is a double-conversion and IGBT-rectifier three phase UPS. With state-of-the-art TLI (Triple Level Inverter) and three phase PFC (power factor correction) topology, the Ultron DPS features industry leading performance of up to 96 % AC-AC efficiency, input power factor &gt; 0.99, output power factor of up to 0.9 and low iTHD &lt; 3%. Aiming to achieve the highest availability possible, Delta has enhanced special designs for battery management, swappable fans and ease of maintenance.  <\/p>\n\n<p>The excellent power performance and high system availability of the Ultron DPS provide customers with the benefits of a stable power supply, high power efficiency, low capital investment and low overall operation cost.<\/p>\n\n<p><strong>Reliability<\/strong><\/p>\n\n<ul class=\"wp-block-list\">\n<li>N X redundancy or hot-standby configuration increases system reliability<\/li>\n\n\n\n<li>Wide input voltage range (DPS 60~120 kVA : -45% ~ 20% ; DPS 160~400 kVA : -40% ~ 20%) allows the UPS to work in harsh electrical environments<\/li>\n\n\n\n<li>Field programmable sequential start-up<\/li>\n\n\n\n<li>Intelligent fan speed control and redundant fan design prevent overheating<\/li>\n\n\n\n<li>Comprehensive battery management sustains battery lifetime and optimal operation<\/li>\n<\/ul>\n\n<p><strong>Low total cost of operation (TCO)<\/strong><\/p>\n\n<ul class=\"wp-block-list\">\n<li>High efficiency even at light load saves operating costs<\/li>\n\n\n\n<li>High input power factor (&gt; 0.99) and low input harmonic distortion (iTHD &lt; 3%) save upstream investment<\/li>\n<\/ul>\n\n<p><strong>Flexibility<\/strong><\/p>\n\n<ul class=\"wp-block-list\">\n<li>The possibility of parallel expansion without the need for additional hardware enables a simple and quick increase in capacity when the performance requirements of the connected technology increase.<\/li>\n<\/ul>\n\n<p><strong>Easy maintenance<\/strong><\/p>\n\n<ul class=\"wp-block-list\">\n<li>Swappable fans reduce maintenance lead time<\/li>\n\n\n\n<li>Built-in manual bypass allows \u201czero downtime\u201d to ensure system availability during service maintenance<\/li>\n\n\n\n<li>Main I\/P, O\/P and bypass switches detection provide quick diagnosis when faults occur.<\/li>\n<\/ul>\n\n<p><strong>Application<\/strong><\/p>\n\n<ul class=\"wp-block-list\">\n<li>Telecommunications<\/li>\n\n\n\n<li>Datacenter<\/li>\n\n\n\n<li>Data centers<\/li>\n\n\n\n<li>Industrial applications<\/li>\n\n\n\n<li>Healthcare sector<\/li>\n\n\n\n<li>Laboratory<\/li>\n\n\n\n<li>Subway<\/li>\n<\/ul>\n","protected":false},"excerpt":{"rendered":"<p>Delta\u2019s Ultron DPS is a double-conversion and IGBT-rectifier three phase UPS. With state-of-the-art TLI (Triple Level Inverter) and three phase PFC (power factor correction) topology, the Ultron DPS features industry leading performance of up to 96 % AC-AC efficiency, input power factor &gt; 0.99, output power factor of up to 0.9 and low iTHD &lt; [&hellip;]<\/p>\n","protected":false},"author":1,"featured_media":7789,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"_acf_changed":false,"footnotes":""},"categories":[136,132],"tags":[],"class_list":["post-8551","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-on-line-vfi-above-to-10-kva","category-ups-systems"],"acf":{"photo_gallery":{"galeria":[[{"id":7789,"title":"UPS_DPS_img","caption":"","full_image_url":"https:\/\/a2b.sk\/wp-content\/uploads\/2024\/03\/UPS_DPS_img.png","thumbnail_image_url":"https:\/\/a2b.sk\/wp-content\/uploads\/2024\/03\/UPS_DPS_img-150x150.png","large_srcset":"https:\/\/a2b.sk\/wp-content\/uploads\/2024\/03\/UPS_DPS_img.png 450w, https:\/\/a2b.sk\/wp-content\/uploads\/2024\/03\/UPS_DPS_img-183x300.png 183w, https:\/\/a2b.sk\/wp-content\/uploads\/2024\/03\/UPS_DPS_img-7x12.png 7w","medium_srcset":"https:\/\/a2b.sk\/wp-content\/uploads\/2024\/03\/UPS_DPS_img-183x300.png 183w, https:\/\/a2b.sk\/wp-content\/uploads\/2024\/03\/UPS_DPS_img-7x12.png 7w, https:\/\/a2b.sk\/wp-content\/uploads\/2024\/03\/UPS_DPS_img.png 450w","media_details":{"width":450,"height":739,"sizes":{"medium":{"file":"UPS_DPS_img-183x300.png","width":183,"height":300,"mime-type":"image\/png","filesize":51239,"source_url":"https:\/\/a2b.sk\/wp-content\/uploads\/2024\/03\/UPS_DPS_img-183x300.png"},"thumbnail":{"file":"UPS_DPS_img-150x150.png","width":150,"height":150,"mime-type":"image\/png","filesize":24798,"source_url":"https:\/\/a2b.sk\/wp-content\/uploads\/2024\/03\/UPS_DPS_img-150x150.png"},"trp-custom-language-flag":{"file":"UPS_DPS_img-7x12.png","width":7,"height":12,"mime-type":"image\/png","filesize":330,"source_url":"https:\/\/a2b.sk\/wp-content\/uploads\/2024\/03\/UPS_DPS_img-7x12.png"}}},"alt_text":"","url":"","target":""}]]}},"yoast_head":"<!-- This site is optimized with the Yoast SEO plugin v23.1 - https:\/\/yoast.com\/wordpress\/plugins\/seo\/ -->\n<title>DPS Series - a2b - energy for the future<\/title>\n<meta name=\"description\" content=\"alternating current sources UPS On-line \/ VFI over 10 kVA DPS Series by A2B\" \/>\n<meta name=\"robots\" content=\"index, follow, max-snippet:-1, max-image-preview:large, max-video-preview:-1\" \/>\n<link rel=\"canonical\" href=\"https:\/\/a2b.sk\/en\/ups-systems\/on-line-vfi-above-to-10-kva\/dps-series\/\" \/>\n<meta property=\"og:locale\" content=\"en_US\" \/>\n<meta property=\"og:type\" content=\"article\" \/>\n<meta property=\"og:title\" content=\"DPS Series - a2b - energy for the future\" \/>\n<meta property=\"og:description\" content=\"alternating current sources UPS On-line \/ VFI over 10 kVA DPS Series by A2B\" \/>\n<meta property=\"og:url\" content=\"https:\/\/a2b.sk\/en\/ups-systems\/on-line-vfi-above-to-10-kva\/dps-series\/\" \/>\n<meta property=\"og:site_name\" content=\"a2b - energy for the future\" \/>\n<meta property=\"article:published_time\" content=\"2024-03-14T08:41:16+00:00\" \/>\n<meta property=\"article:modified_time\" content=\"2024-07-11T08:00:47+00:00\" \/>\n<meta property=\"og:image\" content=\"https:\/\/a2b.sk\/wp-content\/uploads\/2024\/03\/UPS_DPS_img.png\" \/>\n\t<meta property=\"og:image:width\" content=\"450\" \/>\n\t<meta property=\"og:image:height\" content=\"739\" \/>\n\t<meta property=\"og:image:type\" content=\"image\/png\" \/>\n<meta name=\"author\" content=\"martin.skorvanek@gmail.com\" \/>\n<meta name=\"twitter:card\" content=\"summary_large_image\" \/>\n<meta name=\"twitter:label1\" content=\"Written by\" \/>\n\t<meta name=\"twitter:data1\" content=\"martin.skorvanek@gmail.com\" \/>\n\t<meta name=\"twitter:label2\" content=\"Est. reading time\" \/>\n\t<meta name=\"twitter:data2\" content=\"1 minute\" \/>\n<script type=\"application\/ld+json\" class=\"yoast-schema-graph\">{\"@context\":\"https:\/\/schema.org\",\"@graph\":[{\"@type\":\"WebPage\",\"@id\":\"https:\/\/a2b.sk\/en\/ups-systems\/on-line-vfi-above-to-10-kva\/dps-series\/\",\"url\":\"https:\/\/a2b.sk\/en\/ups-systems\/on-line-vfi-above-to-10-kva\/dps-series\/\",\"name\":\"DPS Series - a2b - energy for the future\",\"isPartOf\":{\"@id\":\"https:\/\/a2b.sk\/en\/#website\"},\"primaryImageOfPage\":{\"@id\":\"https:\/\/a2b.sk\/en\/ups-systems\/on-line-vfi-above-to-10-kva\/dps-series\/#primaryimage\"},\"image\":{\"@id\":\"https:\/\/a2b.sk\/en\/ups-systems\/on-line-vfi-above-to-10-kva\/dps-series\/#primaryimage\"},\"thumbnailUrl\":\"https:\/\/a2b.sk\/wp-content\/uploads\/2024\/03\/UPS_DPS_img.png\",\"datePublished\":\"2024-03-14T08:41:16+00:00\",\"dateModified\":\"2024-07-11T08:00:47+00:00\",\"author\":{\"@id\":\"https:\/\/a2b.sk\/en\/#\/schema\/person\/3ecf1d51c0b501778e80355607e57503\"},\"description\":\"alternating current sources UPS On-line \/ VFI over 10 kVA DPS Series by A2B\",\"breadcrumb\":{\"@id\":\"https:\/\/a2b.sk\/en\/ups-systems\/on-line-vfi-above-to-10-kva\/dps-series\/#breadcrumb\"},\"inLanguage\":\"en-US\",\"potentialAction\":[{\"@type\":\"ReadAction\",\"target\":[\"https:\/\/a2b.sk\/en\/ups-systems\/on-line-vfi-above-to-10-kva\/dps-series\/\"]}]},{\"@type\":\"ImageObject\",\"inLanguage\":\"en-US\",\"@id\":\"https:\/\/a2b.sk\/en\/ups-systems\/on-line-vfi-above-to-10-kva\/dps-series\/#primaryimage\",\"url\":\"https:\/\/a2b.sk\/wp-content\/uploads\/2024\/03\/UPS_DPS_img.png\",\"contentUrl\":\"https:\/\/a2b.sk\/wp-content\/uploads\/2024\/03\/UPS_DPS_img.png\",\"width\":450,\"height\":739},{\"@type\":\"BreadcrumbList\",\"@id\":\"https:\/\/a2b.sk\/en\/ups-systems\/on-line-vfi-above-to-10-kva\/dps-series\/#breadcrumb\",\"itemListElement\":[{\"@type\":\"ListItem\",\"position\":1,\"name\":\"UPS systems\",\"item\":\"https:\/\/a2b.sk\/en\/ups-systems\/\"},{\"@type\":\"ListItem\",\"position\":2,\"name\":\"On-line \/ VFI above to 10 kVA\",\"item\":\"https:\/\/a2b.sk\/en\/ups-systems\/on-line-vfi-above-to-10-kva\/\"},{\"@type\":\"ListItem\",\"position\":3,\"name\":\"DPS Series\"}]},{\"@type\":\"WebSite\",\"@id\":\"https:\/\/a2b.sk\/en\/#website\",\"url\":\"https:\/\/a2b.sk\/en\/\",\"name\":\"a2b - energy for the future\",\"description\":\"\",\"potentialAction\":[{\"@type\":\"SearchAction\",\"target\":{\"@type\":\"EntryPoint\",\"urlTemplate\":\"https:\/\/a2b.sk\/en\/?s={search_term_string}\"},\"query-input\":\"required name=search_term_string\"}],\"inLanguage\":\"en-US\"},{\"@type\":\"Person\",\"@id\":\"https:\/\/a2b.sk\/en\/#\/schema\/person\/3ecf1d51c0b501778e80355607e57503\",\"name\":\"martin.skorvanek@gmail.com\",\"image\":{\"@type\":\"ImageObject\",\"inLanguage\":\"en-US\",\"@id\":\"https:\/\/a2b.sk\/en\/#\/schema\/person\/image\/\",\"url\":\"https:\/\/secure.gravatar.com\/avatar\/208dbc3e4fe00b08d9d6c0bb38a0e94d?s=96&d=mm&r=g\",\"contentUrl\":\"https:\/\/secure.gravatar.com\/avatar\/208dbc3e4fe00b08d9d6c0bb38a0e94d?s=96&d=mm&r=g\",\"caption\":\"martin.skorvanek@gmail.com\"},\"sameAs\":[\"https:\/\/a2b.sk\"],\"url\":\"https:\/\/a2b.sk\/en\/author\/martin-skorvanekgmail-com\/\"}]}<\/script>\n<!-- \/ Yoast SEO plugin. -->","yoast_head_json":{"title":"DPS Series - a2b - energy for the future","description":"alternating current sources UPS On-line \/ VFI over 10 kVA DPS Series by A2B","robots":{"index":"index","follow":"follow","max-snippet":"max-snippet:-1","max-image-preview":"max-image-preview:large","max-video-preview":"max-video-preview:-1"},"canonical":"https:\/\/a2b.sk\/en\/ups-systems\/on-line-vfi-above-to-10-kva\/dps-series\/","og_locale":"en_US","og_type":"article","og_title":"DPS Series - a2b - energy for the future","og_description":"alternating current sources UPS On-line \/ VFI over 10 kVA DPS Series by A2B","og_url":"https:\/\/a2b.sk\/en\/ups-systems\/on-line-vfi-above-to-10-kva\/dps-series\/","og_site_name":"a2b - energy for the future","article_published_time":"2024-03-14T08:41:16+00:00","article_modified_time":"2024-07-11T08:00:47+00:00","og_image":[{"width":450,"height":739,"url":"https:\/\/a2b.sk\/wp-content\/uploads\/2024\/03\/UPS_DPS_img.png","type":"image\/png"}],"author":"martin.skorvanek@gmail.com","twitter_card":"summary_large_image","twitter_misc":{"Written by":"martin.skorvanek@gmail.com","Est. reading time":"1 minute"},"schema":{"@context":"https:\/\/schema.org","@graph":[{"@type":"WebPage","@id":"https:\/\/a2b.sk\/en\/ups-systems\/on-line-vfi-above-to-10-kva\/dps-series\/","url":"https:\/\/a2b.sk\/en\/ups-systems\/on-line-vfi-above-to-10-kva\/dps-series\/","name":"DPS Series - a2b - energy for the future","isPartOf":{"@id":"https:\/\/a2b.sk\/en\/#website"},"primaryImageOfPage":{"@id":"https:\/\/a2b.sk\/en\/ups-systems\/on-line-vfi-above-to-10-kva\/dps-series\/#primaryimage"},"image":{"@id":"https:\/\/a2b.sk\/en\/ups-systems\/on-line-vfi-above-to-10-kva\/dps-series\/#primaryimage"},"thumbnailUrl":"https:\/\/a2b.sk\/wp-content\/uploads\/2024\/03\/UPS_DPS_img.png","datePublished":"2024-03-14T08:41:16+00:00","dateModified":"2024-07-11T08:00:47+00:00","author":{"@id":"https:\/\/a2b.sk\/en\/#\/schema\/person\/3ecf1d51c0b501778e80355607e57503"},"description":"alternating current sources UPS On-line \/ VFI over 10 kVA DPS Series by A2B","breadcrumb":{"@id":"https:\/\/a2b.sk\/en\/ups-systems\/on-line-vfi-above-to-10-kva\/dps-series\/#breadcrumb"},"inLanguage":"en-US","potentialAction":[{"@type":"ReadAction","target":["https:\/\/a2b.sk\/en\/ups-systems\/on-line-vfi-above-to-10-kva\/dps-series\/"]}]},{"@type":"ImageObject","inLanguage":"en-US","@id":"https:\/\/a2b.sk\/en\/ups-systems\/on-line-vfi-above-to-10-kva\/dps-series\/#primaryimage","url":"https:\/\/a2b.sk\/wp-content\/uploads\/2024\/03\/UPS_DPS_img.png","contentUrl":"https:\/\/a2b.sk\/wp-content\/uploads\/2024\/03\/UPS_DPS_img.png","width":450,"height":739},{"@type":"BreadcrumbList","@id":"https:\/\/a2b.sk\/en\/ups-systems\/on-line-vfi-above-to-10-kva\/dps-series\/#breadcrumb","itemListElement":[{"@type":"ListItem","position":1,"name":"UPS systems","item":"https:\/\/a2b.sk\/en\/ups-systems\/"},{"@type":"ListItem","position":2,"name":"On-line \/ VFI above to 10 kVA","item":"https:\/\/a2b.sk\/en\/ups-systems\/on-line-vfi-above-to-10-kva\/"},{"@type":"ListItem","position":3,"name":"DPS Series"}]},{"@type":"WebSite","@id":"https:\/\/a2b.sk\/en\/#website","url":"https:\/\/a2b.sk\/en\/","name":"a2b - energy for the future","description":"","potentialAction":[{"@type":"SearchAction","target":{"@type":"EntryPoint","urlTemplate":"https:\/\/a2b.sk\/en\/?s={search_term_string}"},"query-input":"required name=search_term_string"}],"inLanguage":"en-US"},{"@type":"Person","@id":"https:\/\/a2b.sk\/en\/#\/schema\/person\/3ecf1d51c0b501778e80355607e57503","name":"martin.skorvanek@gmail.com","image":{"@type":"ImageObject","inLanguage":"en-US","@id":"https:\/\/a2b.sk\/en\/#\/schema\/person\/image\/","url":"https:\/\/secure.gravatar.com\/avatar\/208dbc3e4fe00b08d9d6c0bb38a0e94d?s=96&d=mm&r=g","contentUrl":"https:\/\/secure.gravatar.com\/avatar\/208dbc3e4fe00b08d9d6c0bb38a0e94d?s=96&d=mm&r=g","caption":"martin.skorvanek@gmail.com"},"sameAs":["https:\/\/a2b.sk"],"url":"https:\/\/a2b.sk\/en\/author\/martin-skorvanekgmail-com\/"}]}},"_links":{"self":[{"href":"https:\/\/a2b.sk\/en\/wp-json\/wp\/v2\/posts\/8551"}],"collection":[{"href":"https:\/\/a2b.sk\/en\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/a2b.sk\/en\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/a2b.sk\/en\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/a2b.sk\/en\/wp-json\/wp\/v2\/comments?post=8551"}],"version-history":[{"count":0,"href":"https:\/\/a2b.sk\/en\/wp-json\/wp\/v2\/posts\/8551\/revisions"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/a2b.sk\/en\/wp-json\/wp\/v2\/media\/7789"}],"wp:attachment":[{"href":"https:\/\/a2b.sk\/en\/wp-json\/wp\/v2\/media?parent=8551"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/a2b.sk\/en\/wp-json\/wp\/v2\/categories?post=8551"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/a2b.sk\/en\/wp-json\/wp\/v2\/tags?post=8551"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}